Generator is very essential part of power system. After all it is main element which can produce power. Any abnormal condition lead to serious damage to generator so to protect generator from various abnormal condition various protection is provided.
15MW Generator Rewinding Process |
Sr No. |
Protection Function |
ANSI Code |
1 |
Differential Protection |
87G |
2 |
Overcurrent Protection |
51 |
3 |
Stator Earth fault Protection |
64G |
4 |
Standby Earth fault Protection |
51N |
5 |
Restricted Earth fault Protection |
64REF |
6 |
Negative sequence Protection |
46 |
7 |
Thermal Overload |
49 |
8 |
Field failure Protection |
40 |
9 |
Low forward Power |
32P |
10 |
Reverse Power protection |
32P |
11 |
V/f Protection |
24G |
12 |
Inadvertent Energization |
51 O/C |
13 |
Under impedance |
21 |
14 |
Voltage Controlled Overcurrent |
51V |
15 |
Out of Step |
78 |
16 |
Interturn Protection |
87IT |
17 |
Under voltage |
27 |
18 |
Over voltage |
59 |
19 |
Residual Overvoltage |
59G |
20 |
Under frequency |
81 |
21 |
Over frequency |
81 |
22 |
Rate of change of frequency |
81R |
23 |
Rotor earth fault Protection |
64R |
Each protection has its own principle to operate, even some protection has specific zone for operation like Differential Protection.
Generator current and voltage is step down to 1A/5A and 110V by Current transformer and Potential transformer respectively and feed to relays.
When numerical relay was not discovered each protection has separate electromechanical relay so generator protection panel was very big and complicated but nowadays only one multifunctional IED (Intelligent electronic device) also called Numerical relay is enough to provide this all protection with accuracy and precision better than electromechanical relays.
Apart from this protections some hard wired tripping is also provided through numerical relay like turbine trip, AVR trip etc.
I have listed some manufacturer. Listed model no.is widely used in power plant as well as industries.
Manufacturer |
Model No. |
SIEMENS |
7UM60 |
AREVA, SCHNEIDER ELECTRIC |
P343 |
ABB |
REM 545 |
L & T |
MG-30 |
Generator Protection P343 in Service |