Generator is very essential part of power system. After all it is main element which can produce power. Any abnormal condition lead to serious damage to generator so to protect generator from various abnormal condition various protection is provided. 

15MW Generator Rewinding Process

            In this post, I am going explain various protection which is provide for generator in power plant for reliable power supply.

Sr No.

Protection Function

ANSI Code

1

Differential Protection

87G

2

Overcurrent Protection

51

3

Stator Earth fault Protection

64G

4

Standby Earth fault Protection

51N

5

Restricted Earth fault Protection

64REF

6

Negative sequence Protection

46

7

Thermal Overload

49

8

Field failure Protection

40

9

Low forward Power

32P

10

Reverse Power protection

32P

11

V/f Protection

24G

12

Inadvertent Energization

51 O/C

13

Under impedance

21

14

Voltage Controlled Overcurrent

51V

15

Out of Step

78

16

Interturn Protection

87IT

17

Under voltage

27

18

Over voltage

59

19

Residual Overvoltage

59G

20

Under frequency

81

21

Over frequency

81

22

Rate of change of frequency

81R

23

Rotor earth fault Protection

64R

              Each protection has its own principle to operate, even some protection has specific zone for operation like Differential Protection. 

         Generator current and voltage is step down to 1A/5A and 110V by Current transformer and Potential transformer respectively and feed to relays. 

            When numerical relay was not discovered each protection has separate electromechanical relay so generator protection panel was very big and complicated but nowadays only one multifunctional IED (Intelligent electronic device) also called Numerical relay is enough to provide this all protection with accuracy and precision better than electromechanical relays.

            Apart from this protections some hard wired tripping is also provided through numerical relay like turbine trip, AVR trip etc.

         I have listed some manufacturer. Listed model no.is widely used in power plant as well as industries.

Manufacturer

Model No.

SIEMENS

7UM60

AREVA, SCHNEIDER ELECTRIC

P343

ABB

REM 545

L & T

MG-30


Generator Protection P343 in Service